The HVA60 VLF/DC Hipot Tester model is the instrument of choice when customers require a single instrument that can test the full range of Medium Voltage cables available - that is 35kV rated cables and below. This very popular, single piece instrument is widely used on long 35/33kV cable systems found in electrical utilities, wind and solar farms, etc.

The HVA60's portable design has a total weight equivalent to just one piece of many two piece VLF 60kV units available on the market. In addition, setting up the HVA60 instrument is simple with no cumbersome interconnects between various modules that make up a typical two-piece design.

Having both VLF AC and DC outputs, the HVA60 is not simply a high voltage instrument for testing MV cables, the unit can also be used for testing Vacuum bottles, cable jackets/sheaths, rotating machines, transformers, switchgear, etc. Test reports are downloaded to the instrument's internal memory or to a USB flash drive.

As with all HVA units, fully automatic test sequences, digital RMS metering, and integrated storage of test results make the HVA60 a top seller.

Features

  • Test your 35kV below MV cable systems.
  • Single Piece Design
  • Weighs only 126 lbs / 57kg
  • Perform tests fully automatically
  • Real time oscilloscope display
  • Insulation Resistance & Cap. measurement
  • RMS Metering of Current and Voltage
  • Output Frequency optimization
  • Internal Storage of Test Reports
  • Download to PC and / or USB flash drive
  • Unlimited duty cycle
  • Bright backlit LCD display
  • Power supply immunity and independence
  • Low maintenance, oil-free design
  • HVA Control Center - User friendly software for immediate, professional detailed reporting and setup

Output Modes

  • VLF 44kVrms / 62kVpk output
  • DC ±60kV
  • VLF Sinewave / Squarewave & DC outputs
  • Cable Jacket / Sheath testing
  • Vacuum bottle testing
  • Fault Conditioning / Fault Trip
  • Load independent output waveform

Safety

  • Remote interlock "kill switch" and HV status indication
  • 12kV power frequency voltage feedback protection
  • Integrated internal discharge of DUT
  • Short circuit detection
  • Local Emergency off button
  • Flashover voltage detection
Transcat Rentals - Rent Equipment from the Industry Leader
   Try Before You Buy
   Save Time & Money
   Weekly and Monthly Rentals
   Access Our Large Inventory
   Long-term Discounts and Rent-to-Buy Options Available

Shop all Rentals

Win a Generac Generator when purchasing $750 or more from Transcat.Win a Generac Generator when purchasing $750 or more from Transcat.
Power Supply/Input Voltage: 110 to 240V AC ±10% (50/60Hz)
Input Power Requirements: 1.5kVA
Rated Max Output Voltage:
Sinusoidal RMS/Peak 44kV / 62kV
Squarewave 60kV
DC ±60kV
Rate Max Output Current:
Sinusoidal RMS 26mA
DC/Squarewave 40mA
Output Frequency (default 0.1Hz): 0.01Hz to 0.1Hz adjustable small increment of 0.01Hz (10 frequencies)
Frequency Optimization: Yes
Maximum Output Load Capability @ MAXIMUM voltage and frequency: 1 µF, *10,000ft, and *3km
Maximum Output Load Capability @ REDUCED voltage and/or frequency: 10 µF, *50,000ft, *15km
Metering:
Voltage 0.1kV Resolution ±1% Accuracy
Current 1 µA Resolution ±1% Accuracy
Capacitance 0.1 nF to 20 µF Range
Resistance 0.1MΩ to 20GΩ Range
Timing Included and integrated
Fast Arc/Flashover Detection included and integrated
Waveform Real time oscilloscope display of actual output voltage waveform
Output Mode (all load independent & symmetrical):
  • VLF AC Sinewave
  • VLF AC Squarewave
  • DC (both Positive and Negative Polarity)
  • Fault Condition Mode / Fault Trip Mode
  • Vacuum Bottle Test Mode (DC) - optional
  • Cable Jacket / Sheath Test Mode
Output Duty: Continuous
Computer Interface:
  • RS232 Standard, USB Flash Memory Download Module (optional)
  • HVA Control Center Software included with every HVA instrument
Memory / Test Record Storage:
Built in Memory 50 Test Records
USB Flash Drive Unlimited (see options)
No. of programmable Automatic Test Sequences: 40
Standard HV Test Lead Cable Included: 15ft / 4.5m
Weight: 126 lbs / 57 kg
Dimensions:
Imperial (inches) 18 x 13.5 x 20.5"
Metric (mm) 450 x 340 x 520 mm
Environmental:
Storage -13°F to 158°F / -25°C to 70°C
Operating 23°F to 113°F / -5°C to +45°C
Humidity 85% RH non-condensing

* Based on typical MV cable. 100pf/ft or 330 pF/m

Note: Due to continuous development, the information may change without notice.

How to Rent from Transcat

Rent from Transcat - Step 1

1. Select Your Rental Product

  • Need help selecting a unit? Try using our Product Finder or search our available units
  • Can’t find what you are looking for? Is the rental unit you need, not available? Give us a call at 800-828-1470 or our chat feature to speak with one of our dedicated Rental Experts
Rent from Transcat - Step 2

2. Contact Our Team of Rental Experts

  • Contact us here or click below to submit your request for a rental quote and a member of our Rental Team will review the request and will reach out to you very soon
Rent from Transcat - Step 3

3. Select Your Rental Period & Complete Your Order

  • Our weekly period lasts 7 calendar days, while our monthly rental period lasts 28 calendar days
  • Provide your form of payment, sign the rental agreement and any other required documents, and we will ship you the unit