AEMC Instruments 6416 Ground Resistance Tester & Clamp Meter

AEMC Instruments 6416 Ground Resistance Tester & Clamp Meter

Order # 2141.01

Mfg # 2141.01

call-regular 800-828-1470
Save 5%
$1,695.00
$1,610.25
Loading...
Loading...
  • Overview
  • Technical Resources
  • Specifications
  • Accessories

AEMC Instruments 6416 Ground Resistance Tester & Clamp Meter

Order # 2141.01 | Mfg # 2141.01
Save 5%
$1,695.00
$1,610.25
Also Available:
Free AEMC 5115

Free AEMC Instruments Pocket DMM

Purchase an AEMC Ground Tester and receive a FREE pocket multimeter, $59 value.
While Supplies Last!

Learn more
arrow_drop_down

Tariff fees or manufacture imposed surcharges may be applicable.

Overview

Product Highlights

The Ground Resistance Tester Model 6416 measures ground rod and grid resistance and impedance without the use of auxiliary rods. Clamp-on ground resistance testers can be used in multi-grounded systems without disconnecting or de-energizing the ground system under test. The Model 6416 simply clamps around the grounding electrode or conductor and measures the resistance to ground. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.

  • Contact Voltage Indication (Warns of Unsafe Conditions)
  • Large Multi-Function Bright Yellow Organic Display (OLED)
  • Selectable Test Frequency (Improves Accuracy in Inductive Environments)
  • Storage of Measurements (O and/or A, V, Inductance with Time-Stamping)
  • Model 6416: up to 300 Measurements Stored
  • Designed to EN 61010-1, 600V CAT IV Safety Standards
  • Clamping Diameter of 1.4” (35mm) with Large Jaw Design
  • Displays Stored Measurements on the LCD Display
  • Auto-Off Power Function
  • Noise Icon And Buzzer Alert User to Presence of Dangerous Voltage and Current Levels
  • Rugged Lexan® Head and Body Construction Resists Breakage

Note:  *Replacement for AEMC 5717E

Each Unit Includes

  • Hard Carrying Case
  • Calibration Loop
  • Four 1.5V AA Batteries
  • User Manual

Technical Resources

Specifications

Ground Resistance Measurement (Auto-Ranging 1 to 199Ω)
Measurement Range Resolution Accuracy
(0.010 to 0.099) Ω 0.001 Ω ±(1.5%Reading +0.01 Ω)
(0.10 to 0.99) Ω 0.01 Ω ±(1.5%Reading +0.02 Ω)
(1 to 49.9) Ω 0.1 Ω ±(1.5% Reading +0.1 Ω)
(50.0 to 99.5) Ω 0.5 Ω ±(2% Reading +0.5 Ω)
(100 to 199) Ω 1 Ω ±(3% Reading +1 Ω)
( 200 to 395) Ω 5 Ω ±(5% Reading +5 Ω)
(400 to 590) Ω 10 Ω ±(10% Reading +10 Ω)
(600 to 1150) Ω 50 Ω 20% approx
(1200 to 1500) Ω 50 Ω 25% approx
Alarm Adjustable from (1 to 199) Ω
Frequency Selection Choice of (50, 60, 128, or 2083) Hz for impedance calculation
Maximum Overload Permanent current: 100 max. 50/60 Hz
Transient current: (<5 s) 200A 50/60 Hz
Current  Measurement Range (Auto-Ranging)
Measurement Range Resolution Accuracy
(0.200 to 0.999) mA 1 µA ±(2 % Reading +50 µA)
(1.000 to 2.990) mA 10 µA ±(2 % Reading +50 µA)
(3.00 to 9.99) mA 10 µA ±(2 % Reading +50 µA)
(10.00 to 29.99) mA 100 µA ±(2 % Reading +100 µA)
(30.0 to 99.9) mA 100 µA ±(2 % Reading +100 µA)
(100 to 299.9) mA 1 mA ±(2 % Reading +1 mA)
(0.300 to 0.990) A 1 mA ±(2 % Reading +1 mA)
(1.000 to 2.999) A 10 mA ±(2 % Reading +10 mA)
(3.00 to 39.99) A 10 mA ±(2 % Reading +10 mA)
Loop Inductance Measurement
Measurement range Resolution Accuracy
(10 to 100) µH 1 µH ±(5 % Reading +1 µH)
(100 to 500) µH 1 µH ±(3 % Reading +1 µH)
Contact Voltage (Touch Voltage) Calculated
Measurement range Resolution Accuracy
(0.1 to 4.9) V 0.1 V ±(5 % Reading +0.1 V)
(5.0 to 49.5) V 0.5 V ±(5 % Reading +0.5 V)
(50 to 75.0) V 1 V ±(10 % Reading +1 V)
General Features
Display OLED, 152 segments (48x39) mm
Memory 300 measurements
Alarm 3 separate alarms (Ω, V and A)
Power Source (4) x1.5 V LR6 (AA) alkaline batteries or 4 NiMH batteries
Battery Life 12 hours or 1440 30-seconds tests approx
Jaw Opening 1.38 in (35 mm) max
Dimensions (2.16 x 3.74 x 10.31) in (55 x 95 x 262) mm
Weight (with Battery) 2.06 lbs (935 g)
Operating Temperature (-4  to +131) °F (-20 to +55) Â°C
Storage Temperature (-22 to +158) °F (-30 to +70) Â°C
Relative Humidity Up to 90 % @ 40 °C
Ingress Protection (IP) IP 40
EMC EN 61326-1
Safety Compliance IEC 61010-1, EN 61010-2-30, EN 61010-2-32, Pollution Degree 2,  600 V CAT IV