Gossen Metrawatt PROFITEST MBASE+

Universal tester for Testing protective devices ac. DIN VDE

Order #: PROFITEST MBASE+

Mfg #: M520S

Questions about availability or need help? Contact Us:

(800) 633-0561
$1,703.00

Gossen Metrawatt PROFITEST MBASE+

Universal tester for Testing protective devices ac. DIN VDE

Order #: PROFITEST MBASE+

Mfg #: M520S

$1,703.00
A broad-range measuring device allows for use of the test instrument in all alternating and 3-phase electrical systems with voltages from 65 to 500 V and frequencies of 15.4 to 420 Hz.
Availability:
Item discontinued

Only need this item for a short time? Learn about rentals

Questions about this product? Speak to an expert

Product Highlights

  • Loop and line impedance measurement
  • Measurement of insulation resistance using nominal voltage, with variable or rising test voltage
  • Low-resistance measurement
  • Earth resistance measurement
  • Standing-surface insulation measurement
  • Universal connector system
  • Testing of residual current devices (RCCBs)
  • Measurement of contact voltage without tripping the RCCB
  • Contact voltage is measured with reference to nominal residual current using 1/3 of the nominal residual current value
  • Tripping test with nominal residual current, tripping time measurement

Special testing for systems and RCCBs

  • Testing of equipment and RCCBs with rising residual current including indication of tripping current and contact voltage at the moment the RCCB is trippedM
  • Testing of RCCBs with: 1/2x, 1x, 2x, 5x IΔN

Special features of the PROFITEST MASTER family

  • EASY transfer stands for direct incorporation of the Profitest Master into DDS-CAD planning software
  • Display of approved fuse types for electrical systems
  • Programable test sequences
  • Energy meter start-up testing
  • Calculation of cable lengths for common copper wire cross-sections
  • Measurement of biasing, leakage and circulating current up to 1 A, as well as working current up to 150 A with the WZ12C current sensor clamp as an accessory
  • Phase sequence measurement (including highest line-to-line voltage)
  • Measurement of contact voltage without tripping the RCCB
  • Contact voltage is measured with reference to nominal residual current using 1/3 of the nominal residual current value
  • Tripping test with nominal residual current, tripping time measurement

Each Unit Includes

  • 1 Test instrument
  • 1 Earthing contact plug insert (country-specific)
  • 1 2-pole measuring adapter and 1 cable for expansion into a 3-pole adapter (PRO-A3-II)
  • 2 Alligator clips
  • 1 Shoulder strap
  • 1 Set of rechargeable batteries (Z502H)
  • 1 Battery charger Z502R
  • 1 Condensed operating instructions
  • 1 Supplement Safety Information
  • 1 DAkkS calibration certificate
  • 1 USB cable

Special Member Pricing
Buy with Calibration
Rental Instruments
Access to 100,000+ products
1,000's of instruments in stock
Product selection expertise
Application assistance
Purchase with a PO