AEMC Instruments 8510 Digital Transformer Ratiometer, (110/220V)
Digital Transformer Ratiometer, (110/220V)

Order #: 2136.50

Mfg #: 2136.50

Questions about availability or need help? Contact Us:

(800) 633-0561
Special Price 3401,00 Regular Price 3580,00

AEMC Instruments 8510 Digital Transformer Ratiometer, (110/220V)

Digital Transformer Ratiometer, (110/220V)

Order #: 2136.50

Mfg #: 2136.50

Special Price 3401,00 Regular Price 3580,00

The DTR® Model 8510 is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR® Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current.

Availability:
In stock

Choose Your Options:

Tariff fees or manufacture imposed surcharges may be applicable.
This item is available as RENTAL at
Call for price
Shop now

Product Highlights

The DTR® Model 8510 is an easy-to-use portable digital transformer turns ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR® Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current.

The DTR® is fully automatic and uses an ANSI/IEEE compliant test method. No user calibration, range selection, hand cranking or tedious balancing is required. At each measurement, the DTR® automatically self-calibrates and checks for open windings/connections/circuit breakers, short circuits (excess excitation current), incorrect test lead placement, and reverse polarity. Measurements are displayed quickly and accurately.

  • Ratio Testing: PT/VT from 0.8000:1 to 8000:1 and CT from 0.8000 to 1000.0 (Auto-Ranging) 
  • Tests performed by exciting the primary and reading the secondary; provides safer conditions for the operator on step-down transformers
  • Continuity test indicates open or loose (high resistance) terminal connections
  • DC test mode eliminates errors due to magnetic build up
  • Stores up to 10 primary/secondary nameplate voltages to use in comparing test results
  • Displays ratio, test current, winding polarity, and deviation from nameplate voltage or ratio
  • Stores up to 10,000 test results
  • DataView® software included which allows configuring the instrument, downloading stored measurements and printing of test results in a report format
  • Display warns of incorrect lead connection, reverse polarity, open and short circuits

Each Unit Includes

  • Includes soft carrying case
  • NiMH batteries (installed)
  • 115V power cord
  • set of (2) 15 ft leads
  • set of (2) alligator clips (red, black)
  • 10 ft USB cable
  • external battery charger (90-264Vac, 50/60Hz)